FM200 is heavier than air and drops down the cabinet and will leak out of any
unsealed gaps around the lower cable enteries.
Specify the weight of Extinguishant to achieve concentration of 7% minimum
in the protected enclosure.
|
FM200 Base Data*A* NFPA2001 |
|
|
|
S.V.V.*1
|
Kgs per m3 at % concentrations of HFC-277ea
|
|
|
|
|
-5
|
0.1241
|
0.5142 |
0.6064 |
0.7005 |
0.7987 |
0.8951 |
|
0
|
0.1268
|
0.5034 |
0.5936 |
0.6858 |
0.78 |
0.8763 |
|
+5
|
0.1294
|
0.4932 |
0.5816 |
0.6719 |
0.7642 |
0.8586 |
|
+10
|
0.1321
|
0.4834 |
0.57 |
0.6585 |
0.749 |
0.8414 |
|
+15
|
0.1347
|
0.474 |
0.5589 |
0.6457 |
0.7344 |
0.8251 |
|
+20
|
0.1373
|
0.465 |
0.5483 |
0.6335 |
0.7205 |
0.8094 |
|
+25
|
0.1399
|
0.4564 |
0.5382 |
0.6217 |
0.7071 |
0.7944 |
|
|
|
|
|
|
|
|
|
*1 Specific Vapor Volume
|
|
|
|
|
|
|
|
|
|
with 800grms @ 20ºC
|
with 1000grms @ 20ºC
|
|
|
Height U |
39U |
42U |
47U |
39U |
42U |
47U |
39U |
42U |
47U |
|
Height Mtr. |
1.9 |
2.0 |
2.2 |
1.9 |
2.0 |
2.2 |
1.9 |
2.0 |
2.2 |
|
|
Volume m3 of Cabinets |
% Concentration @ 20ºC |
% Concentration @ 20ºC |
|
6x6 Rack |
0.68 |
0.72 |
0.79 |
16.01% |
15.21% |
13.83% |
20.06% |
19.06% |
17.32% |
|
6x8 Rack |
0.91 |
0.96 |
1.06 |
12.01% |
11.41% |
10.37% |
15.04% |
14.29% |
12.99% |
|
6x10 Rack |
1.14 |
1.20 |
1.32 |
9.61% |
9.13% |
8.30% |
12.04% |
11.43% |
10.39% |
|
8x6 Rack |
0.91 |
0.96 |
1.06 |
9.00% |
8.55% |
7.78% |
11.28% |
10.72% |
9.74% |
|
8x8 Rack |
1.22 |
1.28 |
1.41 |
7.20% |
6.84% |
6.22% |
9.03% |
8.68% |
7.80% |
|
8x10 Rack |
1.52 |
1.60 |
1.76 |
7.20% |
6.84% |
6.22% |
9.03% |
8.68% |
7.80% |
|
8x12 Rack |
1.82 |
1.92 |
2.11 |
6.00% |
5.70% |
5.18% |
7.52% |
7.15% |
6.50% |
|
|
|
|
|
|
|
M3 filled at % concentration
|
M3 filled at % concentration
|
|
|
-5 |
1.32 |
1.14 |
1.00
|
0.89 |
1.65 |
1.43 |
1.25 |
1.12 |
|
0 |
1.35 |
1.17 |
1.03 |
0.91 |
1.68 |
1.48 |
1.28 |
1.14 |
|
+5 |
1.38 |
1.19 |
1.05 |
0.93 |
1.72 |
1.49 |
1.31 |
1.16 |
|
+10 |
1.40 |
1.21 |
1.07 |
0.96 |
1.75 |
1.52 |
1.34 |
1.19 |
|
+15 |
1.43 |
1.24 |
1.09 |
0.97 |
1.79 |
1.55 |
1.36 |
1.21 |
|
+20 |
1.46 |
1.26 |
1.11 |
0.99 |
1.82 |
1.58 |
1.39 |
1.24 |
|
+25 |
1.49 |
1.29 |
1.13 |
1.01 |
1.86 |
1.61 |
1.41 |
1.26 |
|
|
|
|
|
|
|
FM200, FE227, (HFC-227ea). Worlds most widely used safe-inkind replacement for
Halon 1301. Boils at -16ºC. Has zero ozone depleting potential. It is safe clean
and electrically non-conducting so virtually eliminating collateral damage to
computing and other delicate electronic equipment.
*A Data from NFPA 2001 Standard on Clean Agent Fire Extinguising Systems
*B No consideration for installed Equipment
*C Concentration of Extinguishment in enclosure will increase with rise in
temperature |